Showing all 11 results
Filter
Categories: Clamp meters
DCL1000 | AC Clamp Meter Large Diameter CT 1000A
Function
Range
Accuracy
Resolution
ACA
400/1000A
±(1.7%+5)
0.1A
DCV
400m/4/40/400/600V
±(1.2%+3)
0.1mV
ACV
400m/4/40/400/600V
±(2.2%+5)
0.1mV
Resistance
400/4k/40k/400k/4M/40M Ω
±(1.2%+4)
0.1 Ω
Continuity
Buzzer sounds at between 0Ω and 65Ω (±35V)
Open voltage: approx. 0.4V
Diode test
Open voltage: approx. 1.6V
Sampling rate
3 times/sec.
Bandwidth
ACA 50/60Hz (sine wave)
ACV 50-500Hz (sine wave)
Display
4000
Clamp diameter/Conductor size
42mm/20x54mm
Battery
R03x2
Battery life
Approx. 120 hrs. at DCV (zinc-carbon battery)
Size/Mass
H238xW95xD45mm / Approx. 290g
Safety standards
IEC61010 CATIII 600V
0 Reviews Write a review
Categories: Clamp meters
DCL3000R | True RMS AC Clamp Meter with Flexible Conductor
Specifications
Function
Range
Accuracy
Resolution
ACA
30/300/3000A
±(3.0%+5)
0.01A
Sampling rate
Approx. 2 times/sec.
Bandwidth
45-500Hz
Display
3150
Clamp diameter/Conductor size
Approx. Φ150mm max.
Max. overload protection input
AC5000A
Battery
LR03×2
Battery life
Approx. 130 hrs.
(Alkaline battery / Backlight off)
Size/Mass
H120×W70×D26mm (exc CT) / approx. 300g
Cable length
Approx. 1.8m
Safety standards
IEC61010 CAT.Ⅳ 600V
0 Reviews Write a review
Categories: Clamp meters
DCM2000DR | Clamp Meter AC/DC Max Current 2000A - CAT IV 1000V
Specifications
Function
Range
Accuracy
Resolution
ACA
200.0/2000A
±(2.0%+5)
0.1A
DCA
200.0/2000A
±(2.0%+5)
0.1A
ACV
6.000/60.00/600.0/1000V
±(1.2%+5)
0.001V
DCV
6.000/60.00/600.0/1000V
±(0.5%+5)
0.001V
Resistance
600.0/6.000k/60.00k/600.0k/6.000M/40.00MΩ
±(0.5%+5)
0.1Ω
Frequency
10~1999Hz
±(0.1%+4)
0.01Hz
Capacitance
60n/600n/6μ/60μ/600μ/2000μF
±(2.0%+5)
0.01nF
Continuity
Buzzer sounds at below 10-200Ω Open voltage: approx. 0.5V
Diode test
Open voltage: approx. 1.8V
EF sensing
A voltage or electric field of about 60 V or more is detected. The barr graph and intermittent buzzer beeps change in three steps according to the field intensity. (50/60Hz)
Sampling rate
Approx. 5 times/sec.
Bandwidth
50~400Hz
Display
6000/1999(Hz)
Max. overload protection input
DC/AC1100V
CT: DC/AC2000A
Clamp diameter/Conductor size
Φ55mm/20x66mm
Battery
R6Px2
Battery life
A function: Approx. 80 hrs. Functions other than A: Approx. 240 hrs. (Zinc-carbon battery/Backlight off)
Size/Mass
H264×W97×D43mm/Approx. 640g
Safety standards
IEC61010 CAT Ⅳ 1000V
0 Reviews Write a review
Categories: Clamp meters
DCM301 | AC Clamp Meter with Multimeter Functionality
Specifications
Function
Measuring Range
Accuracy
Resolution
ACA
60.00/600.0/1000A
±(2.5%+5)
0.01A
ACV
6.000/60.00/600.0/1000V
±(1.5%+3)
0.001V
DCV
6.000/60.00/600.0/1000V
±(1%+3)
0.001V
Resistance
6.000k/60.00k/600.0k/6.000M/60.00MΩ
±(2%+5)
0.001kΩ
Frequency
ACV 10Hz-10kHz, ACA 10Hz-2kHz
±(1%+5)
0.1Hz
Capacitance
60.00n/600.0n/6.000µ/60.00µ/600.0µ/6.000m/60.00mF
±(4%+3)
0.01nF
Continuity
Buzzer sounds below 30Ω Open voltage: approx. 1V or less
Detection of Electricity
Buzzer sounds, "-" is shown on LCD, and LED flickers
Detects ACV and EF of approx. 90V or more (50/60Hz)
Sampling rate
Approx. 3 times/sec.
Bandwidth
ACA 45-400Hz ACV 45Hz-1kHz
Display
6000/9999(Hz function)
Clamp diameter/Conductor size
Φ34mm/10×64mm
Battery
LR03×3
Battery life
Approx. 200 hrs.
Size/Mass
H252×W85×D40mm/Approx. 360g
Safety standards
IEC61010 CAT.Ⅳ600V/CAT.Ⅲ1000V
0 Reviews Write a review
Categories: Clamp meters
DCM400 | Basic Digital Clamp Meter with Multimeter Functionality
Specifications
Function
Range
Accuracy
Resistance
ACA
40/400A
±(1.9%+5)
0.01A
ACV
400/600V
±(1.5%+5)
0.1V
DCV
400/600V
±(1%+2)
0.1V
Resistance
400Ω
±(1%+2)
0.1Ω
Frequency (A)
20~4k/10kHz
±(0.1%+1)
1Hz
Frequency (V)
4k/40k/400k/1MHz
±(0.1%+1)
0.001kHz
Continuity
Buzzer sounds at less than approx. 40Ω
Open voltage: approx. 1.5V
Sampling rate
2 times/sec., 20 times/sec. for bar graph
Bandwidth
ACA 50/60Hz: ±(1.9%+5) 60-500Hz: ±(2.5%+5)
ACV 50-500Hz: ±(1.5%+5)
Display
4000
Clamp diameter/Conductor size
Φ25mm/10×34mm
Battery
R03×2
Battery life
Approx. 150 hrs. (Zinc-carbon battery)
Size/Mass
H193×W50×D28mm/Approx. 230g
Safety standards
IEC61010 CAT.Ⅲ300V CAT.Ⅱ600V
0 Reviews Write a review
Categories: Clamp meters
DCM400AD | Clamp Meter for Automotive Maintenance & Digital Multimeter Functions
SPECIFICATIONS
Function
Range
Accuracy
Resolution
ACA
40/400A
±(2%±10)
0.01A
DCA
40/400A
±(2.5%±10)
0.01A
ACV
400/600V
±(1.5%±5)
0.1V
DCV
400/600V
±(1%±2)
0.1V
Resistance
400Ω
±(1%±2)
0.1Ω
Continuity
Buzzer sounds at less than approx. 40Ω
Open voltage: approx. 1.5V
Sampling rate
2 times/sec., 20 times/sec. for bar graph
Bandwidth
50~500Hz
Display
4000
Clamp diameter/Conductor size
Φ25mm/10×34mm
Battery
LR03×2
Battery life
Approx. 50 hrs.(Alkaline battery)
Size/Mass
H193×W50×D28mm/Approx. 230g
Safety standards
IEC 61010 CAT.Ⅲ 300V CAT.Ⅱ 600V
0 Reviews Write a review
Categories: Clamp meters
DCM600DR | Clamp Meter for Automotive Hybrid / Electric Vehicle + DMM Functionality
Specifications
Function
Range
Accuracy
Resolution
Input Impedance
DCA
60/600A
±(2%+5)
0.01A
ACA
60/600A
±(2%+5)
0.01A
DCV
600V
±(1%+2)
0.1V
1MΩ
ACV
600V
±(1.2%+5)
0.1V
Resistance
999.9Ω
±(1%+7)
0.1Ω
Continuity
Buzzer sounds at less than 40Ω
Open voltage: Approx. 2.9V
Sampling rate
3 times/sec.
Bandwidth
50-500Hz
Display
6000
Clamp diameter/Conductor size
Φ30mm/10×50mm
Battery
LR03×2
Battery life
Approx. 40 hrs. (Backlight off)
Size/Mass
H208×W69×D38mm
Approx. 260g
Safety standards
IEC61010 CAT.Ⅲ600V
*In the peak hold mode, the measuring range is fixed at 600A.
0 Reviews Write a review
Categories: Clamp meters
DCM60R | Digital Clamp Meter / Multimeter
Specifications
Function
Range
Accuracy
Resistance
ACA
199.9/600A
±(2%+5)
0.1A
ACV
199.9/600V
±(1.5%+5)
0.1V
Resistance
199.9Ω
±(1.0%+8)
0.1Ω
Continuity
Buzzer sounds at less than 100Ω
Operation method
Δ-Σ method
AC measuring method
True RMS
Sampling rate
2 times / sec
Display
1999 count
Range selection
Auto
Battery low warning
Battery ( ) mark lights at approx. 2.2V or below
Operating temperature / humidity
0℃~40℃, below 80%RH No condensation
Storage temperature / humidity
-10℃~60℃, below 70%RH No condensation
Continuous use time
About 250 hours
Power consumption
Approx. 5.0mW
Safety standards
IEC61010-1, IEC61010-2-030 CAT.III 300V / II 600V
IEC61010-2-032, IEC61010-2-033, IEC61010-31
Bandwidth
50~400Hz
Clamp diameter / Conductor size
25mm / 10 x 30mm
Battery
R03(UM-4) or AAA x 2
Size / Mass
H187 x W50 x D29mm / 210g
Standard accessories included
Test leads (TL-21a), carrying case (C-DCM60L), instruction manual
0 Reviews Write a review
Categories: Clamp meters
DCM660R | True RMS Clamp Meter for Electrical and HVAC Work + DMM Functions
Specifications
Function
Measuring Range
Accuracy
Resolution
Input Impedance
ACA
66/660A
±(2%+5)
0.01A
DCV
600V
±(1%+2)
0.1V
1MΩ
ACV
600V
±(1.2%+5)
0.1V
Frequency (A)
660/6.6k/30k
±(0.2%+1)
0.1Hz
Frequency (V)
660/6.6k/66k/100k
±(0.2%+1)
0.1Hz
Resistance
660Ω
±(1%+7)
0.1Ω
Continuity
Buzzer sounds at less than 30Ω Open voltage: approx. 1.2V
Sampling rate
3 times/sec.
Bandwidth
50-500Hz
Display
6600
Clamp diameter/Conductor size
Φ30mm/10×50mm
Battery
LR03×2
Battery life
Approx. 55 hrs.(Alkaline battery/Backlight off)
Size/Mass
H208×W69×D38mm/Approx. 265g
Safety standards
IEC61010 CAT.Ⅲ600V
0 Reviews Write a review